VMD111/1 Installation Instructions and Technical Specification. Page 3 of 3
VoltMaster: All data refers to MO and SO units unless otherwise stated
Notes:
1 Provide ventilation if installing in cupboard.
2 At full brightness output adjusts to give 11.8V (23.6V) at lamps.
3 Loading capability includes allowance for lamp wattage tolerance.
4 SoftStart operates at switch-on, after mains interruptions and after protection trip delay.
5 For short circuit trip level is very low (no light will show)
6 Use either 8-off terminals or large green terminal.
7 Distribute loads evenly on each side off distribution outlet board if using 8-off terminals.
8 Large green terminal is for wiring to track, high-wire or distribution box.
Condition/feature Requirement (R)/Capability (C) Parameter Value/units Note Type/ comment
Electrical supply (mains input) R Regular sine wave Voltage 207-265V Mandatory Earth
Frequency 48-62Hz must be connected.
Ambient conditions R Non-condensing Temperature 0-45°C 1 VMD300/12, VMD400/24
0-40°C 1 VMD400/12
0-40°C VMDE300/12
Derate for higher temperatures
IP rating IP20
Output C Isolated SELV compatible Nominal 12V 2 VMD300/12 and VMD400/12
VMDE300/12
Voltage 24V 2 VMD400/24
Max. load 300W 3 VMD300/12
(nominal) 400W 3 VMD400/12, VM400/24
Min. load 35W Ensures correct operation
Voltage sensing R 2-wire cable must be Min. cable 2.5mm
2
If sensing cable not connected
connected to track/lamp fitting size to track output freezes at approx half
Min. cable 1mm
2
brightness
size to fused fitting
Sensing cable terminal x 2 Cable size 2.5mm
2
Use load knockout
acceptance
Dimming R Dimming signal terminal Cable size 2.5mm
2
Analogue sig:C1:0V & C4:0-10V
acceptance C1,C2,C3 potentiometer connect
SoftStart C increases output Ramp up 5sec 4 100% effective
slowly from zero time to max.
Overload protection C Trips and reduces Trip 110% ie. trips when overloaded by
output quickly to zero. threshold approx 10% of rated full load
Short circuit protection C Trips and reduces Response <50ms 100% effective
output quickly to zero. time
Recovery after C Soft starts after Total time to 15sec 5 If the fault persists, the output
protection trip approx. 10 second delay recovery continually ramps up to a level
which operates the trip again
Multi outlet units only either: 6
Output terminations. C 8 x fused terminal pairs for Cable size 4mm
2
Total lamp wattage up to individually wired lamp fittings acceptance
maximum load rating Max watts per 100W 7 VMD300/12, VMD400/12
terminal pair 150W 7 VMD400/24
or: 6
C Large Green Cable size 10mm
2
8 Total lamp wattage up to
Terminal pair for track acceptance maximum load rating.
Single outlet units only Ceramic terminal pair Cable size 16mm
2
Output terminations. acceptance
Total lamp wattage up to
maximum load rating
Multi outlet units only One per fused terminal pair As fitted 10A GLASS quick-acting 5 x 20mm
Output fuse rating
Mains supply termination R L, N, Cable size 2x 2.5mm
2
3-way terminal block
(Mandatory Earth) acceptance 2 x 20mm knockout provided
Mains safety fusing R Not customer-replaceable Rating 5A Fast Ceramic 5 x 20mm
Multiload Technology Limited 2 Rosemont Road Hampstead London NW3 6NE Telephone 020 7794 9152 www.multiload.co.uk